Heat Pumps
Heat Pump Covers, Screens and Enclosures: How to Hide the Outdoor Unit in Berkshire and Surrey Gardens Without Hurting It
By Adam Dare
Heat Geek trained installer
Updated 12 November 2026
Reading time
🎉 Named South East Heating Installer of the Year 2026
A heat pump cover can hide the outdoor unit without hurting it if it leaves the clear space the installation manual sets. Vaillant’s aroTHERM plus manual asks for 1 metre above the unit and 600 mm in front of the fan, so an open screen can pass where a lidded box fails. This guide is for Berkshire and Surrey homeowners who want the unit out of sight from the patio.
A cover bought online still has to meet the manual of the unit it sits over. Vaillant’s aroTHERM plus and Grant’s Aerona 290 manuals share a pattern: little room at one end, more at the other, the most in front of the fan or above.
You can cover a heat pump within limits the manufacturer writes into its installation manual. Vaillant gives two reasons for its figures: enough airflow, and room to service the unit. Grant adds air recirculation, where the fan blows cold air at a tall solid barrier and the unit pulls that same air back in, which Grant says cuts both efficiency and output.
Clear space to keep around a ground-mounted unit
Treat these figures as the space a cover or screen must leave, measured from the casing. A lid resting on an aroTHERM plus breaks the 1,000 mm rule above it, however open its slats look. Ask your installer for your own model’s figures before you buy anything.
Products sold as an air source heat pump cover fall into four types, and planting makes a fifth option. Vaillant’s own advice for hiding a unit lists planting, privacy screens, a built heat pump enclosure with louvred doors or hinged panels, and a vinyl wrap, which one of its customers used on an aroTHERM plus to suit a listed barn conversion.
| Airflow | Water and ice | Service access | |
|---|---|---|---|
| Free-standing slatted screen | Open top; stands outside the front and end clearances | Drains as normal | Walk round it |
| Louvred enclosure, open or tall top | Louvres on every face; 1,000 mm clear above an aroTHERM plus | Base stays open to the gravel | Hinged doors or removable panels, as Vaillant suggests |
| Planter or lidded cover | The lid sits inside the space above the unit that both manuals keep clear | Check that the base drains | Planter lifts off for every service |
| Full waterproof cover | Closes the inlet and outlet grilles | Holds meltwater from de-icing inside | Comes off for every service |
| Evergreen planting | Trimmed back to the clearances | Vaillant’s manual says keep the unit away from deciduous trees and shrubs | Keep a path to the service side |
A heat pump acoustic enclosure is a louvred box lined with sound-absorbing material, sold to cut noise toward a neighbour. Vaillant says a well-installed casing can lower the sound by a few decibels, and warns that a casing can sometimes make it louder. For noise, choose the position first and add the box only if the unit still needs one.
Fix the Unit Position on Paper First
Your Blueprint covers where the outdoor unit goes, so you can plan a screen around a fixed position before anything is ordered.
“Eco renewables installed a heat pump for us, we was originally overwhelmed by all the information and different information we was given by different installers. Eco renewables where very clear and put my mind at rest, they did an excellent job and our house is always warm.”
Paul-john Andrews, Google Review
A full cover over a running heat pump in winter closes the two grilles that Vaillant’s manual tells owners to keep clear of snow. Vaillant’s guide to casings says its heat pumps need no cover for protection, and that its heat pumps go through about 300 internal tests before they leave production.
Below 2.5°C
Vaillant’s winter guide says that when the outside air drops below 2.5°C, the aroTHERM plus runs a de-icing cycle for a few minutes, and you may see steam and water coming from the bottom of the unit.
That water has to drain away: Vaillant’s manual asks for a bed of gravel and rubble under a ground-mounted unit, on ground that absorbs water. Vaillant accepts a canopy or free-standing cover against debris and weather, on one condition, good ventilation and airflow. Snow on the casing is normal, Vaillant says; brush it off the grilles, and never pour hot water over a frosted unit.
A side passage beside a detached house hides the unit from the garden. It also puts the unit in a gap between walls or fences, a spot Vaillant’s aroTHERM plus manual tells installers to avoid, along with corners and recesses. Sound bounces between those walls too, and our guide to how loud a heat pump is and where to site it explains why placement comes first.
The heat pump location is fixed at the design stage, before the unit is ordered. Your Blueprint shows where the outdoor unit goes, so a heat pump screen, a planting bed or a new patio can be planned around that spot. Positioning the unit is part of air source heat pump installation, and the manual’s clearances belong in that decision from the start.
In a renovation, settle the unit’s position while the builders are still on site. Pipework can run while ceilings are open, and the base and any screen can go in with the landscaping.
Hand the Position to Your Builder
If building work is planned, get the outdoor unit’s position on paper first and hand it to your builder and garden designer.
“We were fitting a heat pump as part of a ground floor renovation. Adam was great at working around the project, putting pipework in while ceilings were down, liaising with builder and being flexible with dates.”
Lucy Grainger, Google Review
Bracknell Forest Council’s guidance on air source heat pumps (updated 17 October 2025) prefers the unit at the rear of the house. Where that cannot work, the council expects it “screened from view or to blend in with the property”, so in our home borough screening is part of the planning picture as well as the view.
An enclosure can also change the planning position. Part 14 Class G limits the outdoor unit, “including any housing”, to 1.5 cubic metres on a house. A 12 kW aroTHERM plus is about 0.77 cubic metres alone, and heat pump housing that keeps the manual’s clearances is several times that, so check with the council first. Our guide to the planning rules for heat pumps covers the rest.
Larger plots give more choice. Our page on heat pump installation in Sunningdale describes large detached houses with mature gardens; on plots like these, an existing evergreen hedge can screen a unit from outside the clearances.
Yes, if the cover leaves the clearances in the unit’s installation manual. On Vaillant’s aroTHERM plus that means 1,000 mm above, 600 mm in front of the fan and 200 mm behind it in heating mode. A slatted screen or an open louvred enclosure can meet those figures; a lid resting on the unit cannot.
A cover that restricts airflow does. Grant’s Aerona 290 manual says air recirculating from the fan outlet, near tall solid barriers or in enclosed and semi-enclosed spots, reduces efficiency and output. Vaillant says a badly designed casing can reduce efficiency and describes slatted, breathable designs as effective.
Keep it outside the manual’s clearances: on the aroTHERM plus, 600 mm in front of the fan and 100 mm and 500 mm at the two ends; on Grant’s 12 and 15.5 kW models, 1,000 mm in front. Vaillant’s manual also tells installers to avoid sites between walls or between fences.
The permitted development rules for heat pumps count the outdoor unit “including any housing” toward a 1.5 cubic metre limit on a house. An enclosure that keeps the manual’s clearances round the unit can pass that limit on its own, so ask the council before you build one.
Keep a full cover off a running unit. Vaillant’s winter guide says the aroTHERM plus de-ices for a few minutes below 2.5°C and sheds water from its base, and its manual asks for the inlet and outlet grilles to stay clear of snow. Vaillant accepts a ventilated canopy against debris and weather.
In Berkshire and Surrey, start with the position: behind the house where it can go, as Bracknell Forest Council prefers, away from paths and out of narrow gaps between walls. Then add evergreen planting or a slatted screen outside the clearances. For a period house with a narrow plot, our guide to heat pumps in period and older homes covers the wider design questions.
A screen built around the wrong spot gets rebuilt when the unit moves. Settle the position and the model first, check that model’s manual for the clearances, and the cover becomes a straightforward joinery job.
Settle the outdoor unit’s spot in your Blueprint before anything is ordered.